BS 6622 XLPE PVC 8.7/15kV Cable

CHARACTERISTICS

Voltage Rating Uo/U (Um)

8.7/15 (17.5) kV

Temperature Rating

Fixed: 0°C to +90°C

Minimum Bending Radius

Single core - Fixed: 15 x overall diameter 3 core - Fixed: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)


Overview

BS 6622 XLPE PVC 8.7/15kV Cable


APPLICATION

Medium voltage PVC power cables for power networks, underground and in cable ducting.

CHARACTERISTICS

Voltage Rating Uo/U (Um)

8.7/15 (17.5) kV

Temperature Rating

Fixed: 0°C to +90°C

Minimum Bending Radius

Single core - Fixed: 15 x overall diameter 3 core - Fixed: 12 x overall diameter

(Single core 12 x overall diameter and 3 core 10 x overall diameter where bends are positioned adjacent to a joint or termination provided that the bending is carefully controlled by the use of a former)

CONSTRUCTION

Conductor

Class 2 stranded copper conductor

Conductor Screen

Semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation

XLPE (Cross-Linked Polyethylene)

Insulation Screen

Semi-conductive XLPE (Cross-Linked Polyethylene)

Metallic Screen

Individual or collective overall copper tape screen

Filler

PET (Polyethylene Terephthalate) fibres

Separator

Binding tape

Bedding

PVC (Polyvinyl Chloride)

Armour

Single core: AWA (Aluminium Wire Armoured) Multi-core: SWA (Steel Wire Armoured)

Sheath

PVC (Polyvinyl Chloride)

Sheath Colour

Red     Black

STANDARDS

BS 6622, IEC/EN 60228 ,Flame Retardant according to IEC/EN 60332-1-2



Parameter

DIMENSIONS
CONDUCTORS
ELECTRICAL CHARACTERISTICS
DIMENSIONS
NUMBER OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
MINIMUM THICKNESS
mm
NOMINAL THICKNESS OF SEMI CONDUCTIVE LAYER
mm
NOMINAL DIAMETER
mm
NOMINAL WEIGHT
kg/km
InsulationOuter sheathInnerOuterOver insulationOverall
1503.951.320.500.8019.50291400
1703.951.400.500.8021.10311700
1953.951.480.500.8022.80342100
11203.951.480.500.8024.10352350
11503.951.560.500.8026.00372700
11853.951.560.500.8027.30393200
12403.951.640.500.8030.00423750
13003.951.720.500.8032.10454600
14003.951.800.500.8035.00485500
15003.951.880.500.8038.00516750
16303.951.960.500.8042.10568200
3503.952.120.500.8019.50575500
3703.952.200.500.8021.10616500
3953.952.280.500.8022.80657600
31203.952.360.500.8024.10688600
31503.952.520.500.8026.007410500
31853.952.600.500.8027.307711900
32403.952.760.500.8030.008314200
33003.952.840.500.8032.108816600
34003.953.080.500.8035.009519700
35003.953.240.500.8038.0010323600
Expand More
CONDUCTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL DIAMTER OF CONDUCTORNOMINAL SHORT CIRCUIT CURRENT AT 1 SECOND
kA
CONDUCTOR  DC RESISTANCE AT 20 °C
Ω/km
CONDUCTOR  DC RESISTANCE AT 20 °C
Ω/km
508.107.150.3870.497
709.7010.010.2680.344
9511.4013.590.1930.248
12012.7017.160.1530.196
15014.5021.450.1240.160
18515.9026.460.09910.128
24018.6034.320.07540.098
30020.7042.900.06010.080
40023.5057.200.04700.064
50026.5071.500.03660.0510
63030.2090.090.02830.0420
Expand More
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NUMBER OF CORESNOMINAL CROSS SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
A
CONDUCTOR LOSSES IN THE GROUND
kW/km
In ground (20 °C)In air (30 °C)
15024927730.81
17030334531.58
19535841831.78
112040448131.99
115044153731.12
118549361231.11
124056371631.06
130062681131.35
140067690129.25
1500743100628.15
1630---
35021020665.75
37025625767.63
39530731370.12
312034936071.62
315039241073.76
318544346975.36
324051355377.40
330057663579.60
340065073181.10
3500---