Conductor
Stranded Bare Copper (Class 5 According to BS EN 60228:2005)
Insulation : Flame Retardant PVC
Screen : Al-Polyester Tape Foil (100% Coverage)
These Double Screened Cables are used as signal transmission cables in industrial applications. They can be easily used with their flexible construction in narrow applications like Electronic Control Systems of Audio or Computer Systems or in Communication Sector, Electronic Circuits, Measurement Devices, Machine Design, Office Equipment etc. The screening protects the cable from outer electromagnetic interference.
Conductor
Stranded Bare Copper (Class 5 According to BS EN 60228:2005)
Insulation: Flame Retardant PVC
Screen: Al-Polyester Tape Foil (100% Coverage)
Shield: TC Wire Braiding (70% coverage)
Separator: Polyester tape Over Cores
Sheath Color: Flame Retardant PVC
Standard Reference: VDE 812
Flame Retardant: IEC/EN 60332-1
Voltage Rating: 300/500 V
Operating Temperature Range: -20oC to +70oC
Min. Bend Radius: 10 x Overall Diameter
DIMENSIONS | |||||||
No. of core x Nom. Cross Sectional Area (n x mm2) | No. of Strand x Nom. Diameter (n x mm) | Outer Diameter (mm) | Weight (kg/km) | ||||
2 x 0.50 | 16 x 0.20 | 5.2 | 35 | ||||
3 x 0.50 | 16 x 0.20 | 5.5 | 42 | ||||
4 x 0.50 | 16 x 0.20 | 6.0 | 54 | ||||
7 x 0.50 | 16 x 0.20 | 7.2 | 82 | ||||
10 x 0.50 | 16 x 0.20 | 9.0 | 113 | ||||
2 x 0.75 | 24 x 0.20 | 5.7 | 45 | ||||
3 x 0.75 | 24 x 0.20 | 6.0 | 54 | ||||
4 x 0.75 | 24 x 0.20 | 6.5 | 70 | ||||
7 x 0.75 | 24 x 0.20 | 7.9 | 107 | ||||
10 x 0.75 | 24 x 0.20 | 10.2 | 150 | ||||
2 x 1.00 | 32 x 0.20 | 6.1 | 52 | ||||
3 x 1.00 | 32 x 0.20 | 6.4 | 66 | ||||
4 x 1.00 | 32 x 0.20 | 7.0 | 81 | ||||
7 x 1.00 | 32 x 0.20 | 8.5 | 126 | ||||
10 x 1.00 | 32 x 0.20 | 10.8 | 180 | ||||
2 x 1.50 | 30 x 0.25 | 7.0 | 69 | ||||
3 x 1.50 | 30 x 0.25 | 7.4 | 88 | ||||
4 x 1.50 | 30 x 0.25 | 8.2 | 111 | ||||
7 x 1.50 | 30 x 0.25 | 9.9 | 177 | ||||
10 x 1.50 | 30 x 0.25 | 12.7 | 153 |