Maximum operating voltage: 5 kV – 46 kV, 100 and 133% IL
Conductor: Aluminum or Copper Conductor
Conductor Shield: Semi conducting cross-linked polyethylene (XLPE)
Insulation: Thermoset ethylene propylene rubber (EPR)
Insulation Shield: Semi conducting cross-linked polyethylene (XLPE)
Concentric Neutral: Bare Copper Concentric Neutrals
Jacket: Overlying (sleeve) black polyvinyl chloride (PVC)
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Construction
1. Conductor: Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231. On request: strand filled. Sizes: 8 AWG – 1000 kcmil. On request, larger sizes.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE). On request: super clean and super smooth materials.
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request: amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Concentric Neutral: Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced. Full or 1/3 Neutral. On request options: alternate neutral constructions, Water Swellable Powder (WSP), and ripcords.
6. Binder Tape: A suitable polyester tape, as required.
7. Jacket: Extruded Overlying (Sleeve) Black polyvinyl chloride (PVC) sunlight resistant. Configuration: Options. On request: Triplex or Paralleled configurations.
Standards:
ICEA S-94-649 (Concentric Neutral Cables Rated 5 Through 46 kV.)
AEIC CS8 (Extruded Dielectric, Shielded Power Cables rated 5 kV - 46 kV.)
ASTM B8 (Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.)
ASTM B231 (Concentric-Lay-Stranded Aluminum 1350 Conductors.)
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 100% Insulation Level (175 mil) | ||||||||||||
2 | 7 | 0.68 | 6 | 14 | 80 | 1.05 | 646 | 16 | 14 | 80 | 1.05 | 779 |
1 | 19 | 0.71 | 7 | 14 | 80 | 1.09 | 733 | 13 | 12 | 80 | 1.12 | 921 |
1/0 | 19 | 0.75 | 9 | 14 | 80 | 1.13 | 850 | 16 | 12 | 80 | 1.16 | 1075 |
2/0 | 19 | 0.8 | 11 | 14 | 80 | 1.17 | 987 | 13 | 10 | 80 | 1.25 | 1292 |
3/0 | 19 | 0.85 | 14 | 14 | 80 | 1.22 | 1163 | 16 | 10 | 80 | 1.3 | 1530 |
4/0 | 19 | 0.9 | 18 | 14 | 80 | 1.28 | 1385 | 16 | 9 | 80 | 1.38 | 1842 |
250 | 37 | 0.96 | 13 | 12 | 80 | 1.37 | 1576 | 25 | 10 | 80 | 1.41 | 2151 |
350 | 37 | 1.06 | 18 | 12 | 80 | 1.49 | 2075 | 22 | 8 | 80 | 1.59 | 2890 |
500 | 37 | 1.19 | 17 | 10 | 80 | 1.66 | 2814 | 31 | 8 | 110 | 1.78 | 4020 |
750 | 61 | 1.38 | 20 | 9 | 110 | 1.94 | 4095 | — | — | — | — | — |
1000 | 61 | 1.53 | 26 | 9 | 110 | 2.12 | 5268 | — | — | — | — | — |
Aluminum 100% Insulation Level (175 mil) | ||||||||||||
2 | 7 | 0.67 | 6 | 14 | 80 | 1.05 | 503 | 10 | 14 | 80 | 1.05 | 556 |
1 | 19 | 0.71 | 6 | 14 | 80 | 1.08 | 540 | 13 | 14 | 80 | 1.08 | 633 |
1/0 | 19 | 0.75 | 6 | 14 | 80 | 1.12 | 582 | 16 | 14 | 80 | 1.12 | 716 |
2/0 | 19 | 0.8 | 7 | 14 | 80 | 1.17 | 647 | 13 | 12 | 80 | 1.2 | 835 |
3/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 735 | 16 | 12 | 80 | 1.25 | 960 |
4/0 | 19 | 0.9 | 11 | 14 | 80 | 1.27 | 836 | 13 | 10 | 80 | 1.35 | 1141 |
250 | 37 | 0.96 | 13 | 14 | 80 | 1.33 | 930 | 16 | 10 | 80 | 1.41 | 1309 |
350 | 37 | 1.06 | 18 | 14 | 80 | 1.46 | 1174 | 16 | 9 | 80 | 1.56 | 1631 |
500 | 37 | 1.19 | 16 | 12 | 80 | 1.62 | 1495 | 29 | 10 | 80 | 1.66 | 2142 |
750 | 61 | 1.4 | 15 | 10 | 110 | 1.93 | 2153 | — | — | — | — | — |
1000 | 61 | 1.54 | 16 | 9 | 110 | 2.13 | 2715 | — | — | — | — | — |
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 133% Insulation Level (220 mil) | ||||||||||||
2 | 7 | 0.77 | 6 | 14 | 80 | 1.14 | 721 | 16 | 14 | 80 | 1.14 | 855 |
1 | 19 | 0.81 | 7 | 14 | 80 | 1.18 | 812 | 13 | 12 | 80 | 1.21 | 1000 |
1/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 932 | 16 | 12 | 80 | 1.25 | 1157 |
2/0 | 19 | 0.89 | 11 | 14 | 80 | 1.26 | 1072 | 13 | 10 | 80 | 1.34 | 1377 |
3/0 | 19 | 0.94 | 14 | 14 | 80 | 1.31 | 1252 | 16 | 10 | 80 | 1.39 | 1618 |
4/0 | 19 | 1 | 18 | 14 | 80 | 1.37 | 1478 | 16 | 9 | 80 | 1.47 | 1935 |
250 | 37 | 1.05 | 13 | 12 | 80 | 1.48 | 1698 | 25 | 10 | 80 | 1.52 | 2273 |
350 | 37 | 1.16 | 18 | 12 | 80 | 1.58 | 2182 | 22 | 8 | 80 | 1.68 | 2997 |
500 | 37 | 1.28 | 17 | 10 | 110 | 1.82 | 3039 | 31 | 8 | 110 | 1.87 | 4143 |
750 | 61 | 1.47 | 20 | 9 | 110 | 2.03 | 4232 | — | — | — | — | — |
1000 | 61 | 1.62 | 26 | 9 | 110 | 2.21 | 5418 | — | — | — | — | — |
Aluminum 133% Insulation Level (220 mil) | ||||||||||||
2 | 7 | 0.76 | 6 | 14 | 80 | 1.14 | 577 | 10 | 14 | 80 | 1.14 | 631 |
1 | 19 | 0.8 | 6 | 14 | 80 | 1.18 | 617 | 13 | 14 | 80 | 1.18 | 711 |
1/0 | 19 | 0.84 | 6 | 14 | 80 | 1.22 | 663 | 16 | 14 | 80 | 1.22 | 797 |
2/0 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 731 | 13 | 12 | 80 | 1.29 | 919 |
3/0 | 19 | 0.94 | 9 | 14 | 80 | 1.31 | 823 | 16 | 12 | 80 | 1.34 | 1048 |
4/0 | 19 | 0.99 | 11 | 14 | 80 | 1.37 | 928 | 13 | 10 | 80 | 1.44 | 1233 |
250 | 37 | 1.05 | 13 | 14 | 80 | 1.44 | 1050 | 16 | 10 | 80 | 1.52 | 1430 |
350 | 37 | 1.15 | 18 | 14 | 80 | 1.55 | 1279 | 16 | 9 | 80 | 1.65 | 1737 |
500 | 37 | 1.28 | 16 | 12 | 110 | 1.77 | 1718 | 29 | 10 | 110 | 1.81 | 2367 |
750 | 61 | 1.49 | 15 | 10 | 110 | 2.02 | 2289 | — | — | — | — | — |
1000 | 61 | 1.64 | 16 | 9 | 110 | 2.23 | 2864 | — | — | — | — | — |
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 100% Insulation Level (260 mil) | ||||||||||||
1 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 887 | 13 | 12 | 80 | 1.29 | 1076 |
1/0 | 19 | 0.93 | 9 | 14 | 80 | 1.3 | 1010 | 16 | 12 | 80 | 1.33 | 1235 |
2/0 | 19 | 0.97 | 11 | 14 | 80 | 1.34 | 1154 | 13 | 10 | 80 | 1.42 | 1458 |
3/0 | 19 | 1.02 | 14 | 14 | 80 | 1.42 | 1361 | 16 | 10 | 80 | 1.49 | 1727 |
4/0 | 19 | 1.08 | 18 | 14 | 80 | 1.47 | 1591 | 16 | 9 | 80 | 1.57 | 2049 |
250 | 37 | 1.13 | 13 | 12 | 80 | 1.56 | 1792 | 25 | 10 | 80 | 1.6 | 2367 |
350 | 37 | 1.24 | 18 | 12 | 80 | 1.66 | 2282 | 22 | 8 | 110 | 1.82 | 3207 |
500 | 37 | 1.37 | 17 | 10 | 110 | 1.9 | 3154 | 31 | 8 | 110 | 1.95 | 4257 |
750 | 61 | 1.56 | 20 | 9 | 110 | 2.14 | 4408 | — | — | — | — | — |
1000 | 61 | 1.7 | 26 | 9 | 110 | 2.29 | 5558 | — | — | — | — | — |
Aluminum 100% Insulation Level (260 mil) | ||||||||||||
1 | 19 | 0.88 | 6 | 14 | 80 | 1.26 | 692 | 13 | 14 | 80 | 1.26 | 785 |
1/0 | 19 | 0.92 | 6 | 14 | 80 | 1.3 | 741 | 16 | 14 | 80 | 1.3 | 874 |
2/0 | 19 | 0.97 | 7 | 14 | 80 | 1.34 | 812 | 13 | 12 | 80 | 1.37 | 1000 |
3/0 | 19 | 1.02 | 9 | 14 | 80 | 1.41 | 930 | 16 | 12 | 80 | 1.45 | 1155 |
4/0 | 19 | 1.07 | 11 | 14 | 80 | 1.47 | 1040 | 13 | 10 | 80 | 1.54 | 1345 |
250 | 37 | 1.13 | 13 | 14 | 80 | 1.53 | 1143 | 16 | 10 | 80 | 1.6 | 1522 |
350 | 37 | 1.23 | 18 | 14 | 80 | 1.63 | 1379 | 16 | 9 | 110 | 1.79 | 1945 |
500 | 37 | 1.36 | 16 | 12 | 110 | 1.85 | 1831 | 29 | 10 | 110 | 1.9 | 2480 |
750 | 61 | 1.57 | 15 | 10 | 110 | 2.13 | 2464 | — | — | — | — | — |
1000 | 61 | 1.72 | 16 | 9 | 110 | 2.31 | 3003 | — | — | — | — | — |
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 133% Insulation Level (320 mil) | ||||||||||||
1 | 19 | 1.01 | 7 | 14 | 80 | 1.38 | 1011 | 13 | 12 | 80 | 1.41 | 1199 |
1/0 | 19 | 1.05 | 9 | 14 | 80 | 1.44 | 1163 | 16 | 12 | 80 | 1.48 | 1388 |
2/0 | 19 | 1.09 | 11 | 14 | 80 | 1.49 | 1311 | 13 | 10 | 80 | 1.56 | 1616 |
3/0 | 19 | 1.14 | 14 | 14 | 80 | 1.54 | 1501 | 16 | 10 | 80 | 1.61 | 1867 |
4/0 | 19 | 1.2 | 18 | 14 | 80 | 1.59 | 1737 | 16 | 9 | 110 | 1.76 | 2299 |
250 | 37 | 1.26 | 13 | 12 | 80 | 1.68 | 1943 | 25 | 10 | 110 | 1.79 | 2625 |
350 | 37 | 1.36 | 18 | 12 | 110 | 1.85 | 2554 | 22 | 8 | 110 | 1.94 | 3376 |
500 | 37 | 1.49 | 17 | 10 | 110 | 2.02 | 3336 | 31 | 8 | 110 | 2.07 | 4439 |
750 | 61 | 1.68 | 20 | 9 | 110 | 2.27 | 4612 | — | — | — | — | — |
1000 | 61 | 1.83 | 26 | 9 | 110 | 2.42 | 5777 | — | — | — | — | — |
Aluminum 133% Insulation Level (320 mil) | ||||||||||||
1/0 | 19 | 1.05 | 6 | 14 | 80 | 1.44 | 891 | 16 | 14 | 80 | 1.44 | 1024 |
2/0 | 19 | 1.09 | 7 | 14 | 80 | 1.48 | 967 | 13 | 12 | 80 | 1.52 | 1155 |
3/0 | 19 | 1.14 | 9 | 14 | 80 | 1.53 | 1068 | 16 | 12 | 80 | 1.57 | 1293 |
4/0 | 19 | 1.2 | 11 | 14 | 80 | 1.59 | 1183 | 13 | 10 | 80 | 1.67 | 1488 |
250 | 37 | 1.25 | 13 | 14 | 80 | 1.65 | 1292 | 16 | 10 | 110 | 1.79 | 1780 |
350 | 37 | 1.35 | 18 | 14 | 110 | 1.81 | 1648 | 16 | 9 | 110 | 1.91 | 2112 |
500 | 37 | 1.48 | 16 | 12 | 110 | 1.97 | 2011 | 29 | 10 | 110 | 2.02 | 2660 |
750 | 61 | 1.69 | 15 | 10 | 110 | 2.25 | 2668 | — | — | — | — | — |
1000 | 61 | 1.84 | 16 | 9 | 110 | 2.43 | 3222 | — | — | — | — | — |
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 100% Insulation Level (345 mil) | ||||||||||||
1/0 | 19 | 1.1 | 9 | 14 | 80 | 1.5 | 1221 | 16 | 12 | 80 | 1.53 | 1446 |
2/0 | 19 | 1.15 | 11 | 14 | 80 | 1.54 | 1371 | 13 | 10 | 80 | 1.62 | 1676 |
3/0 | 19 | 1.2 | 14 | 14 | 80 | 1.59 | 1563 | 16 | 10 | 80 | 1.67 | 1929 |
4/0 | 19 | 1.25 | 18 | 14 | 80 | 1.65 | 1801 | 16 | 9 | 110 | 1.81 | 2367 |
250 | 37 | 1.31 | 13 | 12 | 110 | 1.8 | 2117 | 25 | 10 | 110 | 1.84 | 2695 |
350 | 37 | 1.41 | 18 | 12 | 110 | 1.9 | 2629 | 22 | 8 | 110 | 2 | 3450 |
500 | 37 | 1.54 | 17 | 10 | 110 | 2.1 | 3464 | 31 | 8 | 110 | 2.16 | 4567 |
750 | 61 | 1.73 | 20 | 9 | 110 | 2.32 | 4701 | — | — | — | — | — |
1000 | 61 | 1.88 | 26 | 9 | 110 | 2.47 | 5872 | — | — | — | — | — |
Aluminum 100% Insulation Level (345 mil) | ||||||||||||
1/0 | 19 | 1.1 | 6 | 14 | 80 | 1.49 | 948 | 16 | 14 | 80 | 1.49 | 1082 |
2/0 | 19 | 1.14 | 7 | 14 | 80 | 1.53 | 1026 | 13 | 12 | 80 | 1.57 | 1214 |
3/0 | 19 | 1.19 | 9 | 14 | 80 | 1.58 | 1129 | 16 | 12 | 80 | 1.62 | 1354 |
4/0 | 19 | 1.25 | 11 | 14 | 80 | 1.64 | 1247 | 13 | 10 | 110 | 1.78 | 1660 |
250 | 37 | 1.3 | 13 | 14 | 110 | 1.76 | 1465 | 16 | 10 | 110 | 1.84 | 1849 |
350 | 37 | 1.4 | 18 | 14 | 110 | 1.86 | 1722 | 16 | 9 | 110 | 1.96 | 2186 |
500 | 37 | 1.53 | 16 | 12 | 110 | 2.06 | 2137 | 29 | 10 | 110 | 2.1 | 2786 |
750 | 61 | 1.74 | 15 | 10 | 110 | 2.3 | 2756 | — | — | — | — | — |
1000 | 61 | 1.89 | 16 | 9 | 110 | 2.48 | 3317 | — | — | — | — | — |
Size AWG or kcmil | Number of Strands | 1/3 Neutral | Full Neutral | |||||||||
Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
Copper 133% Insulation Level (420 mil) | ||||||||||||
1/0 | 19 | 1.25 | 9 | 14 | 80 | 1.65 | 1407 | 16 | 12 | 80 | 1.68 | 1632 |
2/0 | 19 | 1.3 | 11 | 14 | 110 | 1.76 | 1668 | 13 | 10 | 110 | 1.83 | 1978 |
3/0 | 19 | 1.35 | 14 | 14 | 110 | 1.81 | 1869 | 16 | 10 | 110 | 1.88 | 2240 |
4/0 | 19 | 1.4 | 18 | 14 | 110 | 1.86 | 2118 | 16 | 9 | 110 | 1.96 | 2582 |
250 | 37 | 1.46 | 13 | 12 | 110 | 1.95 | 2339 | 25 | 10 | 110 | 1.99 | 2917 |
350 | 37 | 1.56 | 18 | 12 | 110 | 2.08 | 2913 | 22 | 8 | 110 | 2.18 | 3734 |
500 | 37 | 1.69 | 17 | 10 | 110 | 2.26 | 3719 | 31 | 8 | 110 | 2.31 | 4822 |
750 | 61 | 1.88 | 20 | 9 | 110 | 2.47 | 4980 | — | — | — | — | — |
1000 | 61 | 2.03 | 26 | 9 | 110 | 2.62 | 6171 | — | — | — | — | — |
Aluminum 133% Insulation Level (420 mil) | ||||||||||||
1/0 | 19 | 1.25 | 6 | 14 | 80 | 1.64 | 1132 | 16 | 14 | 80 | 1.64 | 1266 |
2/0 | 19 | 1.29 | 7 | 14 | 110 | 1.75 | 1322 | 13 | 12 | 110 | 1.78 | 1512 |
3/0 | 19 | 1.34 | 9 | 14 | 110 | 1.8 | 1434 | 16 | 12 | 110 | 1.83 | 1662 |
4/0 | 19 | 1.4 | 11 | 14 | 110 | 1.86 | 1563 | 13 | 10 | 110 | 1.93 | 1872 |
250 | 37 | 1.45 | 13 | 14 | 110 | 1.91 | 1684 | 16 | 10 | 110 | 1.99 | 2069 |
350 | 37 | 1.56 | 18 | 14 | 110 | 2.04 | 2001 | 16 | 9 | 110 | 2.15 | 2466 |
500 | 37 | 1.68 | 16 | 12 | 110 | 2.21 | 2389 | 29 | 10 | 110 | 2.25 | 3038 |
750 | 61 | 1.89 | 15 | 10 | 110 | 2.46 | 3034 | — | — | — | — | — |
1000 | 61 | 2.04 | 16 | 9 | 110 | 2.63 | 3613 | — | — | — | — | — |